Water Supply, Drainage and Sanitary Requirements in UDCPR 2020
Apr 07, 2024
UDCPR 2020 Chapter 12 is all about the Structural Safety, Water supply, Drainage, and Sanitary Requirements, Outdoor Display, And Other Services in Development Plans as per mentioned in the UDCPR
This is Applicable to all Planning Authorities and Regional Plan Areas except Municipal Corporation of Greater Mumbai, Other Planning Authorities/Special Planning Authorities/ Development Authorities within the limit of Municipal Corporation of Greater Mumbai, MIDC, NAINA, Jawaharlal Nehru Port Trust, Hill Station Municipal Councils, Eco-sensitive/Eco-fragile region notified by MoEF & CC and Lonavala Municipal Council, in Maharashtra.
Rule No. 12.5 Water Supply, Drainage and Sanitary Requirements
1) The planning, design, construction, and installation of water supply, drainage and sanitation, and gas supply systems shall be in accordance with the provisions of Part-9 - Plumbing Services, Section-1 - Water Supply, Drainage and Sanitation, Section-2 - Gas supply of National Building Code of India as amended from time to time.
2) Requirements of Water Supply in Building.
The total requirements of water supply shall be calculated based on the population as given below :-
Occupancy | Basis |
---|---|
Residential Building | 5 persons per tenement |
Other Buildings | No. of persons on occupant load and area of floors given in Table No. 9-E |
3) The requirements of water supply for various occupancies shall be as given in Table No.12-A and Table No.12-B or as specified by the Authority from time to time.
Table No.12-A | ||
---|---|---|
Per Capita Water Requirements for Various Occupancies/Uses | ||
Sr. No. | Type of Occupancy | Consumption per head per day (in liters) |
1 | 2 | 3 |
1 | Residential | |
(a) In living units | 135 | |
(b) Hotels with lodging accommodation (per bed) 180 | 180 | |
2 | Educational | |
(a) Day Schools | 45 | |
(b) Boarding Schools | 135 | |
3 | Institutional (Medical Hospitals) | |
(a) No. of beds not exceeding 100 | 340 | |
(b) No. of beds exceeding 100 | 450 | |
(c) Medical quarters and hostels | 135 | |
4 | Assembly :- Cinema theatres, auditorium, etc. (per seat of accommodation) | 15 |
5 | Government and Semi-public business | 45 |
6 | Mercantile (Commercial) | |
(a) Restaurants (per seat) | 70 | |
(b) Other business buildings | 45 | |
7 | Industrial | |
(a) Factories where bathrooms are to be provided | ||
(b) Factories where no bath-rooms are required to be provided | ||
8 | Storage (including warehousing) | 30 |
9 | Hazardous | 30 |
10 | Intermediate/Stations (excluding mail and express stops) | 45 (25) |
11 | Junction Stations | 70 (45) |
12 | Terminal/Stations | 45 |
13 | International and domestic Airports | 70 |
The value in parenthesis is for stations where bathing facilities are not provided.
Note : The number of persons for Sr.No.(10) to (13) shall be determined by the average number of passengers, handled by the station daily; due consideration may be given to the staff and workers likely to use the facilities.
Table No.12-B | ||
---|---|---|
FLUSHING STORAGE CAPACITIES | ||
Sr. No. | Classification of building | Storage capacity. |
(1) | (2) | (3) |
1 | For tenements having common convenience | 900 litres net per w.c. seat. |
2 | For residential premises other than tenements having common convenience | 270 litres net for one w.c. seat and 180 liters for each additional seat in the same flat. |
3 | For Factories and Workshops | 900 litres per w.c. seat and 180 liters per urinal seat. liters |
4 | For cinemas, public assembly halls, etc | 900 litres per w.c. seat and 350 litres per urinal seat.liters |
Related Regulations
You can visit our other blogs related to Regulations 12 through the below-mentioned links
Signs and Outdoor Display Structures in UDCPR 2020
Drainage and Sanitation Requirements in UDCPR 2020
Alternatives Materials, Methods of Design & Construction, and Tests in UDCPR 2020
Building Services in UDCPR 2020
Quality of Materials and Workmanship in UDCPR 2020